OFP-NV (ESKALIBUR) – fire retardant composition for steel constructions

1. FIELD OF APPLICATION AND PROPERTIES

Fire retardant composition «OFP-NV (ESKALIBUR)» representas a mixture of granulated mineral fiber and non-organic bindingagent.
Coating based on fire retardant compositionOFP-NV (ESKALIBUR) is used for increase of fire rating of metal constructions installed in the internal premises.

2. NORMATIVE AND TECHNICAL REQUIREMENTS

Fire retardant composition OFP-NV (ESKALIBUR) meets the requirements for I group of fire-proof efficiency stated inNPB 236-97 "Fire-proof materials for steel constructions. General requirements. Method of determination of fire-proof efficiency" and can increasefire rating of metal constructions up to 240 minutes.

Certificate of fire safety SSPB.RU.OP019.V01718

Certificate of conformity ROSS RU.AY64.N02393

Hygiene certificate 77.01.03.576.P.006360.02.06

3. TECHNICAL SPECIFICATION

Volume weight of coating, kg/m3, not more

250-350

Bulk weight of dry part, kg/m3, not more

200

Heat conduction coefficient at temperature 2000, W/(m )

0,075

Sound absorbtion

high sound insulation

Combustibility

Class 0

Color

not specified

Reduced thickness of metal, mm

Fire rating and fire-proof efficiency

R60/III group

R90

R120/II group

R150/I group

R240

Layer thickness,
mm

Consumption, kg/m2

Layer thickness,
mm

Consumption, kg/m2

Layer thickness,
mm

Consumption, kg/m2

Layer thickness,
mm

Consumption, kg/m2

Layer thickness,
mm

Consumption, kg/m2

3.4

20

5,00

35

8,75

45

11,25

60

15,00

72

18,00

> 4.1

18

4,50

30

7,50

40

10,00

50

12,50

65

16,25

> 6.0

15

3,75

25

6,25

35

8,75

45

11,25

55

13,75

>10.0

12

3,00

18

4,50

25

6,25

35

8,75

45

11,25

> 15.0

10

2,50

12

3,00

15

3,75

25

6,25

40

10,00

4. SURFACE TREATMENT

Coating should be applied on the primed load bearing metal constructions. The recommended anticorrosion coatings: “GF-021” (glyptal base primer), Akrilak EP primer (epoxy base primer). Dust and dirt should be removed from the surface by means of wet rags, grease and oil stains can be removed with solvent (solvent 646 is recommended). If application of solvent is not possible use the washing agents.

5. APPLICATION

Application conditions:

Ambient temperature - not less than +5 °;

Relative air humidity - not more than85 %;

Temperature of surface for application of paint should be 3 above condensation point.

Layer of primer solution is to be applied prior to application of fire retardant composition OFP-NV (ESKALIBUR). Primer solution should be prepared by means of mixing polymer with water. Concentration of polymer in primer solution makes 25-30 mass%. Application of primer solution is performedby means of high pressure machines of airless sprayingor manually by brush or roller. Fire retardant compund is to be applied on wet layer of primer solution.

Application modes:

Application is performed mechanically by means of gunning machines (ISO-40, ISO Mini Jet). Consumption of compositionfor layer of 10 mm thickness makes 2.5 kg/m2, excl. losses. Required thickness of layer is reached in one pass according to the required fire rating. Final drying time - 7 days. If it is necessary toincreasewaterproofing properties or due to design requirements it is allowed to apply enamel of thickness 50-70 micron after preliminary smoothing of surface.

Cleaning of tools:

Wash the tools with water immediately after end of work.

6. OPERATING CONDITIONS AND LIFITIME OF COATING

Operation temperature: from -50 0Ѡto +50 0

Operation of coating in the enclosed premises with relative humidity not more than 90%. Avoiddirect ingress of moisture on the coating.

Lifetime of coating is not limited.

7. PACKAGING AND STORING

Fire retardant composition OFP-NV (ESKALIBUR)is supplied in bags of25 kg.